Building pressure testing Building Envelope Leakage Testing

Building Envelope Leakage Testing Ltd

Specialists in air leakage testing of all types of buildings

25 Hampton Way, Llanfaes, Beaumaris, Anglesey, North Wales, LL58 8LG, UK
Tel. 01248 811585 Fax. 01248 811586

Building air leakage testing Building pressure testing
Air leakage testing Home Contact Us About Us   Building Envelope Leakage Testing

Building air leakage test Building air leakage test Air leakage testing Air leakage testing

All our testing is completed to follow Technical Standard 1 of the Air Tightness Testing and Measurement Association (ATTMA)

 

Building Air Leakage Testing

What is air leakage & what impact does it have?
Building air leakage & energy efficiency

We use fan pressurisation testing of buildings to show compliance with Part L of the Building Regulations. Pressurisation testing equipment ranges from single and multiple fan units, to large truck mounted fan systems. The following table shows recommended air leakage specifications for different building types.

Air Leakage Index (m3/hr/ m2 @ 50Pa)

Building Type Best Practice Normal
Offices (naturally ventilated) 3.0 7.0
Offices (mixed mode) 2.5 5.0
Offices (air conditioned/low energy) 2.0 5.0
Factories/Warehouses 2.0 6.0
Superstores 1.0 5.0
Schools 3.0 9.0
Hospitals 5.0 9.0
Museums and Archival Stores 1.0 1.5
Cold Stores 0.2 0.35
Dwellings (naturally ventilated) 3.0 9.0
Dwellings (mechanically ventilated) 3.0 5.0


The air leakage test involves connecting the fans to a suitable aperture in the building envelope, usually a double door opening. The fans are variable speed and therefore variable volume.
With the test rig connected to the building the pressure will be increased in 5.0 Pa increments from 10.0 Pa to 60 Pa or the maximum that can be achieved. Then 5.0 Pa decrements down to 10 Pa. At the time of the tests the barometric pressure is recorded as well as the internal and external temperatures.
All the logged readings are used to calculate the air leakage rate at 50 Pa standard atmosphere. Should the building pass then a witness certificate must be signed by the builders representative.
It is anticipated that the work can be carried out in one day. We will only require the building to be free of personnel for a period of approximately1.0 hour at any one time.

The local wind speed should preferably be below 3.0m/s.
Before the test is carried out, all mechanical ventilation systems must be switched off.
All extract and supply terminals need to be sealed of with plywood sheeting or plastic sheeting and gaffer tape.
Trickle vents and smoke vents must be closed but not sealed
Drain traps should be filled.
All internal doors wedged open to equalise the internal pressure.
Opening windows and external doors must be shut.

Air permeability testing of buildings to comply with Part L of Building Regulations